The Energy Department today announced that the General Services Administration’s (GSA) United States Court House in Wichita, Kansas is the winner of the 2013 Better Buildings Federal Award. The Better Buildings Federal Award challenges agencies to achieve the greatest reduction in annual energy intensity, or energy consumed per gross square foot. This year’s winner cut its energy intensity by 20% and saved over $40,000 in utility costs in the 12 month competition period.
The Energy Department today announced that the General Services Administration’s (GSA) United States Court House in Wichita, Kansas is the winner of the 2013 Better Buildings Federal Award. The Better Buildings Federal Award challenges agencies to achieve the greatest reduction in annual energy intensity, or energy consumed per gross square foot. This year’s winner cut its energy intensity by 20% and saved over $40,000 in utility costs in the 12 month competition period.
Building on past energy efficiency improvements funded through the American Recovery and Reinvestment Act, GSA Region 6 implemented energy efficiency upgrades, including a cost-effective re-tuning of building control systems and equipment, to boost energy efficiency in the 80-year-old Wichita Court House in Wichita, Kansas. GSA also provided training and technical support to the building staff on how best to manage and sustain the energy efficiency improvements and also encouraged Court House tenants to reduce energy waste within their work areas. Despite the summer’s heat waves and the winter’s cold snaps, GSA cut energy use by 20% in the building while maintaining a satisfaction rate among tenants of more than 90%, according to a GSA Tenant Satisfaction Survey.
Finalists from the U.S. Army, the U.S. Air Force, and the Departments of State and Energy also competed in this year’s race to reduce their buildings’ energy intensity. When selecting finalists, the Energy Department's Federal Energy Management Program (FEMP) considered energy efficiency measures deployed in each facility; best practices in energy management; and building operations undertaken by facility personnel, as well as organizational programs and tools to encourage broad sustainability efforts.
Beginning in 2014, the Better Buildings Federal Award will be presented to the federal facility that achieves the highest ranking in the Environmental Protection Agency's National Building Competition, Battle of the Buildings, which challenges federal, commercial, and industrial buildings to achieve the greatest reduction in annual energy use intensity. Participants will measure, track, and report their monthly 2014 energy consumption using EPA's online energy tracking tool, Portfolio Manager, and compare it to calendar year 2013 usage.
In 2012, GSA Region 6 undertook a Targeted E4 (Energy Efficiency
Expert Evaluation) project to "target" no-cost and low-cost retuning of
building control systems and equipment to improve energy efficiency. The
Targeted E4 provided technical support to the building staff and
operations and maintenance (O&M) contractors to assist in retuning
building controls schedules and sequences and to provide training on how
best to manage and sustain the improvements.
Targeted E4 energy-saving retuning actions included:
Targeted E4 energy-saving retuning actions included:
-
Static pressure and supply air temperature reset on the air-handling units
-
Optimal Start for all air-handling units
-
Zero minimum outside air when AHUs operate during unoccupied periods
-
Seasonal manual adjustments to chiller and pump valves
-
Integration of chiller control with the building automation
system which allowed chillers to be scheduled "as needed" rather than
run on 24/7 schedule during the summer cooling season. This modification
also enabled the BAS system to control chilled water temperature reset
thereby providing additional savings during non-peak cooling months
-
Installation of timer controls on parking garage air handling
make-up air and exhaust fans not controlled by the BAS system allowed
the building staff to synchronize the garage AHU operation with tenant
occupancy and thereby reduce unnecessary after-hours equipment usage
-
Reduced run times of building exhaust fans by adjusting existing timers
-
Installed digital timers on parking garage lighting circuits,
allowing more precise timer control while reducing hours of illumination
-
Installed LED bulbs on several lights that are on night light circuits.